TROUBLESHOOTINGSPLIT AIR CONDITIONERWITH HEAT PUMPSOPHIA

Seite 2

1.3.2 Indoor / outdoor unit’s communication diagnosis and solution(E1) Error Code E1 Malfunction decision conditions Indoor unit does not receive the

Seite 3

Remark: Use a multimeter to test the DC voltage between 2 port and 3 port of outdoor unit. The red pin of multimeter connects with 2 port while t

Seite 4 - 3W- 10m1%

1.3.3 Zero crossing detection error diagnosis and solution (E2) Error Code E2 Malfunction decision conditions When PCB does not receive zero crossing

Seite 5 - 4 - WA Y

1.3.4 Fan speed has been out of control diagnosis and solution(E3) Error Code E3/F5 Malfunction decision conditions When indoor fan speed keeps too lo

Seite 6

Index 1: 1:Indoor or Outdoor DC Fan Motor(control chip is in fan motor) Power on and when the unit is in standby, measure the voltage of pin1-pin3, p

Seite 7 - HI GHL OW

1.3.5 Open circuit or short circuit of temperature sensor diagnosis and solution(E5) Error Code E4/E5/F1/F2/F3 Malfunction decision conditions If the

Seite 8 - I C1 424C08

1.3.6 Refrigerant Leakage Detection diagnosis and solution(EC) Error Code EC Malfunction decision conditions Define the evaporator coil temp.T2 of th

Seite 9 - 1.3 Diagnosis and Solution

1.3.6 Overload current protection diagnosis and solution(F0) Error Code F0 Malfunction decision conditions An abnormal current rise is detected by che

Seite 10

1.3.7 IPM malfunction or IGBT over-strong current protection diagnosis and solution(P0) Error Code P0 Malfunction decision conditions When the voltag

Seite 11

For example: P-U P-V Note: The photos below are only for reference, it’s may be not same totally with the ones on your side.

Seite 12 - Check if the connections and

1.1 Indoor Unit Error Display Operation lamp Timer lamp Display LED STATUS ☆ 1 time X E0 Indoor unit EEPROM parameter error ☆ 2 times X E1 Indoo

Seite 14

N-V N-W

Seite 15 - E4/E5/F1/F2/F3

For 30K~36K: At first test the resistance between every two ports of U, V, W of IPM and P, N. If any result of them is 0 or close to 0, the IPM is def

Seite 17 - Compressor checking]. Is it

1.3.8 Over voltage or too low voltage protection diagnosis and solution(P1) Error Code P1 Malfunction decision conditions An abnormal voltage rise or

Seite 18 - ● Outdoor PCB faulty

1.3.9 High temperature protection of IPM module or compressor top diagnosis and solution(P2) Error Code P2 Malfunction decision conditions If the samp

Seite 19 - For example:

1.3.10 Inverter compressor drive error diagnosis and solution(P4) Error Code P4 Malfunction decision conditions An abnormal inverter compressor drive

Seite 20

Digital tester Normal resistance value Digital tester Normal resistance value (+)Red (-)Black ∞ (Several MΩ) (+)Red (-)Black ∞ (Several MΩ) P N U N U

Seite 21

1.3.11 Low pressure protection diagnosis and solution(P6) Error Code P6 Malfunction decision conditions When the pressure of system reach a certai

Seite 22

Main parts check 1. Temperature sensor checking Disconnect the temperature sensor from PCB, measure the resistance value with a tester. Temperature

Seite 23

1.2 Outdoor unit error display(TBD) For CH-09SPH-115VO, CH-12SPH-115VO, CH-09SPH-230VO, CH-12SPH-230VO, N11712200001919511[ 1. 6] 2015- 09- 30US- K

Seite 24 - ● System leakage or block

Appendix 1 Temperature Sensor Resistance Value Table for T1,T2,T3,T4 (°C--K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm -20 -4 115.266 20 68

Seite 25 - Measure the resistance

Appendix 2 Temperature Sensor Resistance Value Table for TP (°C --K) °C °F K Ohm °C °F K Ohm °C °F K Ohm °C °F K Ohm -20 -4 542.7 20 68 68.66

Seite 26

Appendix 3: ΔT(℉) =9ΔT(℃)5 °C °F °C °F °C °F °C °F °C °F -5 23 21 69.8 51 123.8 82 179.6 113 235.4 -4 24.8 22 71.6 52 125.6 83 181.4 114 237.

Seite 27

Appendix 4 1. Normal voltage of P and N 208-240V(1-phase,3-phase) 380-420V(3-phase) In standby around 310VDC around 530VDC In operation With passiv

Seite 28 - ● PCB faulty

2. Compressor checking Measure the resistance value of each winding by using the tester. Position Resistance Value ASN98D22UFZ ASM135D23UFZ ATF235

Seite 29

3. Fan Motor Measure the resistance value of each winding by using the tester. Model YKT-32-6-202L YKT-32-6-3L YKT-48-6-206 YKT-63-6-200L Brand

Seite 30

4. Pressure On Service Port Cooling chart: °F(°C) ODT IDT 75 (23.89) 85 (29.44) 95 (35) 105 (40.56) 115 (46.11) BAR 70/59 8.2 7.8 8.1 8.6

Seite 31

Heating Chart: °F (°C) ODT IDT 57/53 (13.89/11.67) 47/43 (8.33/6.11) 37/33 (2.78/0.56) 27/23 (-2.78/-5) 17/13 (-8.33/-10.56) BAR 55 30.3 28.5

Seite 32

1 Front panel How to remove the front panel. 1) Pull the below side of the panel toward you and remove screw of the cover. 2) Release the connector

Seite 33

2 Electrical parts How to remove the electrical parts. 1) Remove the front panel from procedure 1. 2) Pull out the room temp. sensor (T1). Remove

Seite 34

For CH-09SPH-230VO, CH-12SPH-230VO, CH-18SPH-230VO, CH-18SPH-230VO +T4TPT3NLHNNRd iHa v eLow-FreYESNONoUBL UEVREDWBLACKTESTPORTP MVDC- F ANDR_ LDR

Seite 35 - 3. Fan Motor

For CH-24SPH-230VO, Suct i onExhaust+17122200000309Hu i QiTe s t Po r t11HEAT4 - WA YWBL UEBLACKREDVUTPT3T4NoNONOYESLow- Fr

Seite 36 - Cooling chart:

After power on, LED3(Green color) and LED2(Red color) will be flash if the unit has some problems. No. Problems LED3 (Green) LED2 (Red) IU display 1

Seite 37 - 2.1 Indoor unit

For CH-S30FTXW-SV, CH-S36FTXW-SV, NLSHOW/ SWEARTH[ 1. 4] 2014. 06. 26EU- KFR105W/ BP3T5N1- 350S. D. 13. WP1- 1L - OUTN- OUTCONNECT TO INVERTER driver

Seite 38 - ①1 screw

IPM board, 202302141237PF C- L2[ 1. 6] 20 14 . 10. 16EU- KFR105W/ BP2T3N1- 350( 767) . D. 13. MP2- 1PF C- L1EARTH+CN55T O- MA I NWVUI P M2I P M1I C1

Seite 39

1.3 Diagnosis and Solution 1.3.1 EEPROM parameter error diagnosis and solution(E0/F4) Error Code E0/F4 Malfunction decision conditions Indoor or outd