HIGH-WALL DUCTLESSAIR CONDITIONING &HEATING SYSTEMINSTALLATION MANUALSOPHIAIMPORTANT NOTE:Read this manual carefully before installing or operatin
Page 10 Unit Parts3Installation OverviewFig. 2.1NOTE ON ILLUSTRATIONSIllustrations in this manual are for explanatory purposes. The actual shape of
Page 11 Indoor Unit Installation4Installation Instructions – Indoor UnitPRIOR TO INSTALLATIONBefore installing the indoor unit, refer to the label
Page 12 Refer to the following diagram to ensure proper distance from walls and ceiling:Step 2: Attach mounting plate to wallThe mounting plate is
Page 13 4in (101mm)7.05in(179mm)5.35in(136mm)1.45in (37mm)11.4in (290mm)1.95in (49mm)Left rear wall hole 2.5in (65mm)Right rear wall hole 2.5in (65
Page 14 CAUTIONBe extremely careful not to dent or damage the piping while bending them away from the unit. Any dents in the piping will aect the
Page 15 Step 5: Connect drain hoseBy default, the drain hose is attached to the left-hand side of unit (when you’re facing the back of the unit). H
Page 16 BEFORE PERFORMING ELECTRICAL WORK, READ THESE REGULATIONS 1. All wiring must comply with local and national electrical codes, and must be
Page 17 Step 6: Connect signal cableThe signal cable enables communication between the indoor and outdoor units. You must first choose the right cab
Page 18 6. Feed the signal wire through this slot, from the back of the unit to the front.7. Facing the front of the unit, match the wire colors
Page 19 If refrigerant piping is already embedded in the wall, do the following:1. Hook the top of the indoor unit on the upper hook of the mounti
Table of ContentsInstallation ManualIndoor Unit Installation ...111. Select installation location ... 112. Attach mountin
Page 20 Outdoor Unit Installation5Installation Instructions – Outdoor UnitStep 1: Select installation locationBefore installing the outdoor unit, y
Page 21 SPECIAL CONSIDERATIONS FOR EXTREME WEATHERIf the unit is exposed to heavy wind:Install unit so that air outlet fan is at a 90° angle to the
Page 22 If you will install the unit on the ground or on a concrete mounting platform , do the following:1. Mark the positions for four expansion
Page 23 If you will install the unit on a wall-mounted bracket, do the following: CAUTIONBefore installing a wall-mounted unit, make sure that the
Page 24 WARNING 1. Prepare the cable for connection:USE THE RIGHT CABLE • Indoor Power Cable (if applicable): H05VV-F or H0
Page 25 Refrigerant Piping Connection 6Note on Pipe LengthThe length of refrigerant piping will aect the performance and energy efficiency of the u
Page 26 DO NOT DEFORM PIPE WHILE CUTTINGBe extra careful not to damage, dent, or deform the pipe while cutting. This will drastically reduce the
Page 27 6. Place aring tool onto the form.7. Turn the handle of the aring tool clockwise until the pipe is fully ared.8. Remove the aring to
Page 28 Instructions for Connecting Piping to Outdoor Unit1. Unscrew the cover from the packed valve on the side of the outdoor unit. (See Fig. 5
Page 29 Air Evacuation7Preparations and PrecautionsAir and foreign matter in the refrigerant circuit can cause abnormal rises in pressure, which ca
Refrigerant Piping Connection ...25A. Note on Pipe Length ... 25B. Connection Instr
Page 30 3. Open the Low Pressure side of the manifold gauge. Keep the High Pressure side closed.4. Turn on the vacuum pump to evacuate the system
Page 31 Electrical and Gas Leak Checks8Electrical Safety ChecksAfter installation, confirm that all electrical wiring is installed in accordance wit
Page 32 Test Run9Before Test RunOnly perform test run after you have completed the following steps:• Electrical Safety Checks – Confirm that the un
Page 33 DOUBLE-CHECK PIPE CONNECTIONSDuring operation, the pressure of the refrigerant circuit will increase. This may reveal leaks that were not p
Cooper and Hunter © 2016For your convenience, please record the model and serial numbers of your new equipment inthe spaces provided. This information
CS368I-AB16122000002333 20151121www.cooperandhunter.us
Page 4 This symbol indicates that ignoring instructions may cause death or serious injury.This symbol indicates that ignoring instructions may caus
Page 5 WARNING6. For all electrical work, follow all local and national wiring standards, regulations, and the Installation Manual. You must use
NameShape Quantity1111(for cooling & heatingmodels only)Clip anchorMounting plate xing screw ST3.9 X 25Remote controller Fixing screw for remote
111Owner’s manualInstallation manualQuick Start Guide Page 7 NameShape QuantityParts you must purc hase. Consul t the dealer about the pipe si ze.
Page 8 Select Installation Location (Page 11)Attach Mounting Plate(Page 12)Drill Wall Hole(Page 12)Installation Summary - Indoor Unit2Installation
Page 9 Mount Indoor Unit(Page 18)STEP 8Wrap Piping and Cable (Page 18)1(L)2(N) 3(S)Connect Piping(Page 25)Connect Wiring(Page 17)Prepare Drain Hose